SWITCHGEAR CEP 14/15

 

SINGLE-PHASE NETWORK / THREE-PHASE NETWORK 

SWITCHGEAR CEP14/15

 
AUGIER switchgears are specifically designed to power extensive 950V, 3200V, 5500V, 6600V networks. The switchgear compartments can be equipped with a cut out switch or appropriate contactor depending on the operating voltage.

CEP 14 : Single-phase network - CEP 15 : Three-phase network
 


BENEFITS OF CEP 14 - 15

 A switchgear can include two or three stacked compartments. You choose the function of a compartment to suit requirements. The full cabinet is in the ‘protected’ category, IP 3XC, grey-coloured, RAL 7035 and 7016, and is for indoor use. The frames are made of folded and welded steel sheets and the separations are made of welded or screwed steel sheets. The switchgears have a compact design. The compartments with pluggable carriage perform the visible cut-out essential for safety.Due to their design, the switchgears do not require rear access. To open the doors and to remove the mobile carriages completely, a gap at the front measuring roughly 1200 mm is sufficient (minimum: 1000 mm). The complete isolation of an outgoing feeder is achieved by unplugging the contactor carriage and by closing the earthing switch and the cut out circuit switch on the outgoing feeder cable.

A switchboard panel is made up of several switchgears placed side by side, joined together electrically by a busbar located in the busbar compartment.

  • VISIBLE CUT-OFF PLUGGABLE CARRIAGE
     
  • SECURITY : LOCKING BY LOCKS
     
  • INTUITIVE TOUCH SCREEN INTERFACE
     
  • ELECTRICAL PROTECTIONS ADAPTED TO THE ROAD LIGHTING NETWORK
     
  • DISPLAY FOR VOLTAGE, CURRENT, NETWORK POWER RATING
 
 

FEATURES OF CEP 14 - 15

These characteristics apply in operating temperatures of between 0°C and +55°C and at altitudes of less than 1000 metres.

  • OPERATING VOLTAGE Classe 7,2 kV
  • NOMINAL FREQUENCY 50 Hz
  • DIELECTIC BEHAVIOUR 20 kV - 50 Hz - 1 minute
  • NOMINAL INTENSITY 300 A
  • THERMAL BEHAVIOUR 3200 A - 1 seconde
  • ELECTRODYNAMIC BEHAVIOUR 8300 A crête
  • TRANSFORMER WITH DRY INSULATION RATIO 100/0,1
  • TRANSFORMER WITH DRY INSULATION POWER 0,05 VA
  • TRANSFORMER WITH DRY INSULATION CLASS 10P10
  • TRANSFORMER WITH DRY INSULATION POWER DC THERMAL CURRENT 80Ipn, 1s soit 8000A eff

 

 